Cabinet

  • Material: Stainless steel or Painted AluZinc
  • Size: (HxWxD) 400 x 400 x 210 mm
  • Weight: 31 kg
  • Classification: IP 64
  • Temperature Range: -40oC ... +60oC
  • Voltage Supply: 115/230 VAC* (6-33 kV)
  • Heating Element: 30 W
  • Battery: 2 x 12V, 12 Ah rechargeable lead acid batteries
  • Charging Current: 2.5 A
  • Current Consumption: 0.14 A DC (stand-by)

Radius RNO Radio

Frequency Range:

  • VHF 140 - 174 MHz
  • UHF 330 - 350 MHz
  • UHF 360 - 390 MHz
  • UHF 400 - 430 MHz
  • UHF 430 - 440 MHz
  • UHF 440 - 470 MHz
  • UHF 475 - 505 MHz

Tx Power: 0.01 W - 5.0 W software adjustable
Receiver Sensitivity: -110 to -118 @ BER

Standards:

  • FCC RULE PARTS: 90.210
  • ETSI 300-220/UHF HIGH 300-113
  • ETS 300-683
  • MPT1329
  • MPT1411
  • LVD 72/23/EEC (93/68/EEC)

3rd party communication

NMS 100 can be supplied, as an option, with a DNP3, IEC 60870-5-101 or IEC 60870-5-104 protocol interface, allowing it to be integrated into an existing SCADA system.

T20 control panel

  • Loss of Volts
    • Indicates if the NMS 100 has lost voltage supply.
  • EFI/FPI1-3 Operated
    • Indicates earth fault on the power line.
  • Cct 1-3 Earth Selected
    • Indicates earth switch selected.
  • Charger Fail
    • LED indicates if there is a charger failure.
  • Fuse Alarm
    • Indicates if the fuse is broken.
  • Battery Alarm
    • Indicates if the battery voltage is below configured level.
  • Battery Test
    • Checks the condition of the batteries.
  • Battery Faulty
    • Indicates when the condition of the batteries is below required performance.
  • Open/Close
    • To open or close the switch with double command button ”Control Enable”.
    • Indicates the position of the switch.
  • In Service
    • Indicates when the unit is powered.
  • Lamp Test
    • Activation and indication of lamp test for LEDs.
  • Configuration Port
    • 9 pin. D-sub configuration port.
  • Circuit 1-3
    • For setting the identification of the disconnector or switch.
  • Local/Off/Supervisory
    • To set the NMS 100 to local or supervisory mode with maneuver handle.