LinkedIn.png   Twitter.png   Google-+Icon.png

PDR 300

Radio transceiver

  • Data rates:
    • 4800/9600 bps @ 12.5 kHz
    • 9600/19200 bps @ 25 kHz
  • Frequency range options:
    • UHF 400...470 MHz
    • VHF 135...175 MHz
  • Operation modes: Half duplex, simplex
  • Modulation: 4FSK, V.23
  • Forward error correction: Yes, with interleaving (4FSK)
  • Collision avoidance: Yes, configurable
  • Repeating: Multi-repeating, up to 6 repeaters on one path
  • Number of remote radios per master: 300
  • Encryption: 128-bit XTEA
  • Tx Power: Adjustable, 0.001…5.0 W
  • Receiver sensitivity: −100…−116 dBm @ BER < 10−6 depending on data rate, channel spacing and frequency

Temperature requirements

  • Compliance with radio standards: −20…+55°C
  • Functional: −40…+75°C

Physical dimensions

  • Size: H51 × W192 × D114 mm
  • Weight: 900 g

Power supply requirements

  • Voltage: Nominal 12...24 VDC (10.8...30.0 VDC)
  • Maximum current: 1.4 A at 5 W Tx and 24 V

Connections

  • Main power supply: 2-pole, female, 5.08 mm pitch; isolated from chassis
  • Antenna: BNC, female
  • Serial ports: 2 × RS-232 DB9 female, both wired as DCE (modem), isolated from chassis
  • COM port data rate: 600…57600 bps
  • CFG port data rate: 600...115200 bps
  • Ethernet ports: 2 × 10/100Base-T
  • Ethernet port protocols: TCP/IP, UDP/IP

Configuration Interface

  • Software: Standard Windows terminal software
  • Connection type: RS-232 or Ethernet (SSH)
  • Serial data rate: Selectable 1200/9600/57600 bps

 LED indicators

  • CPU
  • Configuration mode
  • System Detect
  • Carrier Detect
  • Radio Tx, Radio Rx
  • Configuration Tx, Configuration Rx
  • COM Tx, COM Rx

RNI 12 Application Software

Supported protocols

  • R3
  • R4, R4E, R4E2, R4E3

Compatibility

  • RNI 12 v2
  • RNI 12
  • RNI 11

Repeating

  • Five repeater jumps
  • Two possible repeater paths

 

RNO 401 Application Software

Supported protocols

  • With concentrator: R4E, R4E2, R4E3
  • With IED: DNP3

Compatibility

  • RNO 401 v2

Repeating

  • Five repeater jumps
  • Two possible repeater paths

 

RNO 501 Application Software

Supported protocols

  • With concentrator: R4E, R4E2, R4E3
  • With IED: DNP3

Compatibility

  • RNO 501 v2

Repeating

  • Five repeater jumps
  • Two possible repeater paths